High frequency dual conversion online design; Modular design;
Mainly used in scenarios such as data centers and computing sites;
Provide stable and pure AC power supply for customer loads.
Excellent load adaptability; High input power factor;
Dual conversion pure online architecture, zero conversion time for battery mains power supply mode switching, supporting fixed frequency output, effectively ensuring load power supply reliability
Adopting advanced DSP digital control technology to provide stable and reliable sine wave power supply
90V~300V wide input voltage and 40~70Hz frequency input range, compatible with harsh power environments, reducing battery discharge times and improving battery life
| input parameters | |
|---|---|
| Number of input lines | Single phase two-wire (L, N) protective ground |
| Input voltage range | High Voltage Version HV: Zero Fire Phase Voltage: 90~300VAC |
| Input frequency range | 440Hz-70Hz |
| Input power factor | ≥0.99 |
| output parameters | |
|---|---|
| Number of output lines | Single phase two-wire (L, N) protective ground |
| rated voltage | High voltage version HV: 208/220/230/240VAC |
| Output voltage accuracy | ±1% |
| output frequency | 50/60 ± 4Hz (phase-locked following mains)/50/60Hz ± 0.1% (fixed frequency mode) |
| output waveform | pure sine wave |
| Output Distortion (THDV%) | <2% (linear load)> |
| overload capacity | 10 minutes @ 105%~125% rated load/1 minute @ 125%~150% rated load/0.5 seconds @>150% rated load |
| Battery and Charger | |
|---|---|
| Battery voltage/quantity | 192/240VDC (external) external 16/20 cells, other battery voltages can be customized |
| charging current | Long lasting machine (external battery): 4A |
| structural shape | |
|---|---|
| Box form | rack-mounted |
| Rack mounted dimensions | UPS host: 440mm (width) x 88mm (2U) (height) x 493mm (depth) without battery/battery box: 440mm (width) x 132mm (3U) (height) x 500mm (depth) |
| Weight (kg) | 10.0 |
| human-machine interface | |
|---|---|
| LCD display | Display input and output voltage, frequency, load percentage, operating mode, machine status |
| communication interface | Standard RS232 |
| Optional accessories | Optional SNMP monitoring card/RS485 MODBUS communication card/LAN (TCP IP) - MODBUS communication card/AS400 dry socket card |
| environmental parameters | |
|---|---|
| Working temperature range | 0~40oC |
| Working humidity range | 0-98% (non condensing) |
| noise | <50db> |